The chlorine is neutralized using caustic solution. The unit is designed based on
risk analysis study to prevent release of chlorine directly into atmosphere.
The scenario considered are:
Instantaneous high flow rate
Chlorine concentration
Scrubbing efficiency
The chlorine concentration should be monitored continuously near the toner and should
be ensured that concentration is less than 3 ppm
Air flow rate required
Fusible plug worst case in the 150 lb toner (68 Kg)
For 150 lb cylinder, gas leak rate is 20 lbs/min = 110 scfm
Considering safety factor, suction air flow required is 250 CFM to evacuate entire
chlorine gas from leakage area.
Chlorine Neutralization
In the scrubber system, Chlorine is neutralized by using sodium hydroxide and gives
by product of sodium hypochlorite and sodium chloride.
Cl2 + 2 NaOH → NaOCl + NaCl + H2O
Major Components in Scrubber
Chlorine sensor
FRP Capturing hood with actuated damper
FRP Ducting
FRP scrubber system
Caustic recirculation pumps
FRP blower
FRP exhaust chimney
Features
Cleanand chemical resistant interior
Sash stop limit and air flow monitoring system
Optional -Sensors for activating alarm when gas leaks out of the
hood.
Operation of scrubber system
One common duct will run along the length of chlorine storage area, chlorine tank
filling and loading area. Tonners containing chlorine will be connected online with
chlorine sensor. All the tonners will be provided with an online chlorine gas
monitoring system with hood to cover the toner, nozzle and connection manifolds.
The hood part has bottom portion and top portion, of which top portion is removable
when it is required to change the toner. Whenever the chlorine tanks are to be
connected/removed from the online system, the top portion will be removed and placed
after keeping the toner. When both hoods, bottom portion and top portion are placed,
it creates a fully closed system, thus preventing the chlorine escape out of hoods.
The electrically actuated damper will be provided for each hood, connected with each
toner. All the hoods are connected to main ducting line which is connected to the
scrubber. The damper is controlled by PLC based controller system. All the dampers
are in closed condition normally. When the chlorine gets leaked in a particular
toner, it will be detected by sensor and the signal will be sent to PLC controller
system. Then, automatically the damper of leakage toner hood will be turned on and
the scrubber and blower will be switched on without any human intervention.
Once the system starts, it will create negative suction near the leakage hood and
pulls out entire leaked chlorine to the scrubber system. The scrubber will
neutralize the chlorine gas by caustic solution and will leave treated gas to the
atmosphere via blower and chimney.
The scrubber system consist of three section. 1 Spray section and 2 Packed bed
section. The inlet gas from the hood enters horizontally in spray section where 15%
caustic solution is sprayed with high pressure at cross current direction to scrub
the chlorine. This section handles extremely high concentration of chlorine. After
passing through the spray section, it enters into the packed bed section, it acts as
polishing section to increase scrubbing efficiency.
The entire chlorine gas is neutralized before releasing into the atmosphere. The
scrubber is capable of reducing the inlet chlorine gas concentration to less than 5
ppm at the outlet. A pre-treatment stage (spray section) handles extremely high
concentrations while subsequent high-efficiency stages remove the remainder of the
toxic vapors. During catastrophic releases, the scrubber achieves more than 99.999%
chlorine vapor removal efficiency.
Typical Scrubbing Products Liquid chemicals that have been used to scrub chlorine
include:
Sodium hydroxide
Potassium hydroxide
Sodium carbonate
Calcium hydroxide
Hydrogen peroxide
Sodium hydroxide solutions are the most commonly used for typical scrubbing
applications. However, the other chemicals listed above have been successfully used
in many applications where they may be readily available, less expensive or satisfy
the specific application.
Drizgas Tech is one of leading manufacturer of Emergency chlorine scrubber in India.
We provide highly efficient, top-quality scrubber system built around your precise
requirements. Contact us with your process information so we can begin discussing
the type of new equipment that best fits your situation.
Features
Factory-assembled for easy installation
Proven in independent testing under a catastrophic one-ton gas release
Skid-mounted
Compact, low profile enables indoor installations
FRP construction for strength and corrosion resistance
Integral secondary containment
Heat trace and insulation
Designed to contain and treat up to eight 150-lb chlorine cylinders
Minimum maintenance at remote, unmanned locations